Advance Static VAR Generator (ASVG)
โพสต์เมื่อ : 17 พ.ย 2566 เวลา 1:4 น.
| Items | Sinexcel Ultra Series ASVG | ||
|---|---|---|---|
| Rating | 30K | 50K | 100K |
| Function | 2nd~13rd harmonic, reactive power and three-phase unbalance compensation | ||
| System parameters | |||
| Nominal voltage | 380/400/415V (228-456V) | ||
| L-N voltage | 220/230/240V (132-264V) | ||
| Nominal frequence | 50/60Hz, auto sensing (Range : 45Hz~62.5Hz) | ||
| Parallel quantities | 380/400/415V (228-456V) | ||
| Efficiency | 99% | 98.5% | |
| Connection type | 3 Phase 3 Wire / 3 Phase 4 Wire | ||
| CT location | Load / Supply side | ||
| Performance indicators | |||
| Control algorithm | FFT, intelligent FFT, and instantaneous reactive power | ||
| Fast response Time | < 5us | ||
| Full response Time | < 5ms | ||
| Target power factor | Adjustable from -1 to +l | ||
| Switching frequency | Average 40kHz,up to 95kHz | ||
| Cooling air requirement | 180CEM | 240CFM | |
| Noise level | <60dB (Full load) | <65dB (Full load) | |
| Communications ports | RS485 and Ethernet port(R.J45) | ||
| Communications protocols | Modbus RTU. TCP/IP | ||
| Module display interface | 4.3-inch HMI(module), 7-inch HMI(central monitor) and LED | ||
| Protection functions | Over-voltage protection, under-voltage protection, inverter bridge inverse protection, over-compensation protection and so on | ||
| Mounting type | Wall-mounted, Rack-mounted and Cabinet | ||
| Dimensions(Wx DxH mm) | 500*470*88 | 500*520*100 | |
| Net weight | 24kg | 32kg | |
| Storage temperature | -40°C~70°C | ||
| Operating Ambient temperature | -10°C~40°C (may derate capacity if ambient temperature exceeds 40°C) | ||
| Relative humidity | 5% to 95%, non-condensing | ||
| Altitude | <1500m, 1500-4000m, capacity is derating 1% for every 100m altitude increased. | ||
| Protection class | IP20 (IP degree can be customizable) | ||